Integrating to a building management system

Modbus RTU over RS-485 for Nordicco HVLS fans

Based on “Advanced Operations – Integrating to a Building Management System”, vers. 1.7.Open the PDF

Draft: this guide has not yet been approved by Nordicco’s technical team. The printed manual applies if they differ.

Your installation

The guide shows only the steps that apply to these answers.

Fans on the line
Parity (DIP switch 2, position 6)
Baud rate (position 7)
Address (position 8)
Inputs wired at the drive

Leave empty when only Modbus is wired.

0 of 27 ticked off

Before you start

Warning: Get written approval before you open the drive

Safety-criticalManual p. 2

Connecting to the Modbus terminals requires accessing the NORDICCO® system drive, which voids the warranty unless prior written approval has been obtained from the manufacturer.

Contact Nordicco (+45 73 70 90 83, info@nordicco.eu) before you start.

A couple of key things to consider before you start

The drive speaks Modbus RTU on a two-wire RS-485 line

The fan is a Modbus slave; the BMS is the master and asks one fan at a time. How such a line is built – topology, cable, terminations, biasing, addresses, serial settings – is laid down in the MODBUS over Serial Line specification and implementation guide V1.02 (modbus.org). This guide refers to it by section, and says where the drive differs from it.